Schneider A9V44463 | Vigi iC60 – earth leakage add-on block – 4P – 63A – 300mA – AC type
Technical Specifications A9V44463
-
Product Code: A9V44463
-
Series: Vigi iC60
-
Device Type: Earth Leakage Add-on Block
-
Number of Poles: 4 (3 phases + neutral)
-
Rated Current (In): 63 A
-
Residual Operating Current (IΔn): 300 mA
-
Leakage Detection Type: Type AC (sinusoidal residual currents)
-
Rated Operational Voltage: 400 V AC
-
Rated Frequency: 50/60 Hz
-
Mounting Type: DIN rail (on iC60 MCBs)
-
Test Button: Yes
-
Degree of Protection: IP20 (front panel)
-
Standards: IEC 61008-1, IEC 60947-2
-
Mechanical Durability: > 5000 cycles
-
Electrical Endurance: > 2000 operations at rated load
Key Features
-
4-Pole Protection: Covers all three phases and neutral, ideal for three-phase installations.
-
High Current Rating: Rated at 63A, suitable for medium to high-load circuits.
-
300mA Sensitivity: Designed for indirect contact protection and fire prevention, rather than personal protection (which usually uses 30mA).
-
Type AC Leakage Detection: Handles sinusoidal AC leakage, appropriate for most general-purpose electrical systems.
-
Compatible with iC60 Breakers: Designed to attach directly to Schneider iC60 series circuit breakers.
-
Test Functionality: Integrated test button for routine maintenance and functionality checks.
-
Quick Mounting: Tool-less DIN rail mounting simplifies installation and upgrades.
Applications
The Schneider A9V44463 is suited for a wide range of use cases, especially in scenarios where earth fault protection is required but high leakage levels are permissible.
Industrial Applications
-
Suitable for factories, production lines, and heavy machinery setups where operational leakage may be higher than residential limits.
Fire Protection
-
The 300mA sensitivity allows detection of leakage currents that could cause thermal stress and lead to electrical fires, even if not harmful to humans.
Three-Phase Systems
-
Perfect for commercial buildings, large HVAC units, pumping stations, and three-phase distribution boards requiring residual current protection on all lines.
Panel Upgrades
-
Easy to add to existing iC60 breakers, offering a straightforward way to enhance safety without replacing the full distribution system






There are no reviews yet.