. Technical Specifications A9R14280

  • Brand: Schneider Electric

  • Product Series: Acti9 iID

  • Model Number: A9R14280

  • Device Type: RCCB (Residual Current Circuit Breaker)

  • Number of Poles: 2 Poles

  • Rated Current (In): 80 Amperes

  • Rated Residual Operating Current (IΔn): 300 mA

  • Sensitivity Type: Type AC (detects pure AC sinusoidal residual currents)

  • Rated Voltage (Ue): 230/240V AC (single-phase)

  • Frequency: 50/60 Hz

  • Short-Circuit Withstand: 6 kA (when used with backup protection)

  • Mounting: DIN rail, 2 modules wide (36 mm)

  • Degree of Protection: IP20 (front panel), IP40 (in suitable enclosure)

  • Operating Temperature: -25°C to +60°C

  • Electrical Endurance: 10,000 operations (typical)

  • Standard Compliance: IEC/EN 61008-1

. Key Features

  • High Current Rating (80A): Suitable for main circuit protection in high-demand installations.

  • 300mA Sensitivity: Provides protection against fire hazards caused by high earth leakage currents.

  • Type AC Detection: Suitable for typical domestic and commercial applications where only AC leakage is expected.

  • Dual-Pole Switching: Disconnects both phase and neutral for improved safety and isolation.

  • Compact Design: Takes only 2 DIN modules (36 mm), ideal for use in modern switchboards.

  • Mechanical Indicator: Clearly displays ON/OFF/trip status for fast fault identification.

  • Integrated Test Button: For regular function testing to ensure device integrity.

  • No Load Protection: Should be paired with a circuit breaker (MCB) for overcurrent protection.

  • Tool-Free Installation: Designed for fast and easy DIN rail mounting.

. Applications

The A9R14280 RCCB is primarily used for equipment and fire protection, rather than personal shock protection, due to its 300mA residual current rating. Suitable applications include:

  • Main Incoming Protection: In residential and commercial distribution panels.

  • Fire Prevention: Detects high leakage currents that may lead to overheating or fire, especially in aging electrical systems.

  • Large Residential Installations: Protection for entire houses or villas with high current requirements.

  • Commercial Buildings: Offices, retail spaces, or small industrial workshops requiring robust leakage protection.

  • Sub-Distribution Boards: For partial or segmented protection of large installations.